Home About us Contact | |||
Synchronous Generator (synchronous + generator)
Selected AbstractsEffects of intermediate load on damping of synchronous generatorEUROPEAN TRANSACTIONS ON ELECTRICAL POWER, Issue 4 2006P. Aree Abstract The transfer-function block-diagram model of a single-machine infinite-bus power system, originally developed by Heffron and Phillips, has been a popular analytical tool amongst power system engineers for explanation and assessment of synchronous generator dynamic behaviors. Since this model simply accounts for the generator field circuit with none of the damper circuits, it may not always give a realistic transient response. Moreover, the model considers only a grid-system load without local and intermediate loads. Hence, effects of these loads together with the damper circuits on electromechanical damping have not yet been completely studied. In this paper, the Heffron-Phillips's model has been advanced to incorporate an intermediate load plus one additional damper circuit in the q -axis. The upgraded model demonstrates a great influence of the intermediate load together with the q -axis damper circuit on the electromechanical damping and the dynamic interaction between the field and damper flux linkages. The study shows the key contributions of load to rise and fall of the damping. It appears that the electromechanical damping can be improved with regard to the unity power-factor load through increasing in the natural damping and decreasing in the automatic voltage regulator (AVR) negative damping torques. Nevertheless, the damping is mostly declined, when the load power factor is poor. Moreover, it is markedly changed in relation to various locations of load. The damping characteristics of synchronous generator are investigated using the eigenvalue and frequency response methods. Copyright © 2006 John Wiley & Sons, Ltd. [source] Required limiting impedance and capacity of fault current limiter installed in customer system with synchronous generatorIEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, Issue 3 2006Daisuke Iioka Member Abstract We investigated the required limiting impedance and capacity of a fault current limiter (FCL) installed at an incoming feeder of a customer system with a synchronous generator in a utility distribution system. It was assumed that two types of FCL were installed, i.e. a resistive type (R-type) FCL and an inductive type (L-type) FCL. A fault current out of the customer system and a voltage in the customer system were calculated following a three-phase, short-circuit fault occurrence. It was found that the required type of FCL and the required limiting impedance depended on the rated capacity of the generator in order to obtain the suppression of the fault current under 0.1 kAS and to maintain of customer voltage between 85 and 100% of the nominal voltage (6.6 kV). The capacity of FCL consisting of the smallest limiting impedance is discussed. © 2006 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc. [source] |